PROFIBUS
36/54
 

2.2.3 Hybrid connector (part two)


Read the manufacturer’s instructions, these instructions may provide important information about the connector design and use.
 


IP 67 connectors generally consist of several parts. Open the package and ensure that all parts are available.

Should there be no manual delivered from the manufacturer please see the following describtions and use them as a guideline. These desribtions are:

  1. open the Connector.



  2. Pass the cable through the screwed gland and any other parts of the connector that are required.



  3. Strip the insulation from the cable; ensure that the stripped cable dimensions are applicable to the connector you are using (observe the manufacturer’s data).

               

  4. Strip the insulation from the cores.



  5. Crimp the contacts onto the cable cores.



  6. Insert the contacts in the appropriate connector block openings.



  7. Connect the cable shield.



  8. fasten the screwed gland to provide strain relief.

  9. Close the connector.


 
   
36/54